N2XSEY 3 x (50-300) mm² 18/30 kV

Cu / XLPE / CTS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
50 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
50 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
50 69.0 5,294
70 73.5 6,326
95 77.0 7,410
120 81.0 8,466
150 84.5 9,600
185 88.5 11,005
240 93.5 13,151
300 99.0 15,481

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
50 0.387 0.494 0.421 227 203 7.15 1.37
70 0.268 0.342 0.396 280 248 10.01 1.37
95 0.193 0.247 0.378 338 296 13.59 1.37
120 0.153 0.196 0.364 387 336 17.16 1.37
150 0.124 0.159 0.351 438 377 21.45 1.37
185 0.0991 0.128 0.340 498 425 26.46 1.37
240 0.0754 0.098 0.326 583 491 34.32 1.37
300 0.0601 0.079 0.315 660 552 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information