N2XSEY 3 x (35-300) mm² 12/20 kV

Cu / XLPE / CTS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
35 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
35 54.5 3,501
50 57.0 4,026
70 61.0 4,917
95 65.0 5,960
120 68.5 6,909
150 72.5 8,039
185 76.5 9,374
240 82.0 11,458
300 86.5 13,563

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
35 0.524 0.668 0.395 188 173 5.01 1.03
50 0.387 0.494 0.379 223 203 7.15 1.03
70 0.268 0.342 0.357 277 249 10.01 1.03
95 0.193 0.247 0.341 334 297 13.59 1.37
120 0.153 0.196 0.328 384 337 17.16 1.37
150 0.124 0.159 0.318 433 377 21.45 1.37
185 0.0991 0.128 0.308 494 425 26.46 1.37
240 0.0754 0.098 0.296 578 491 34.32 1.37
300 0.0601 0.079 0.287 657 552 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information