N2XSEY 3 x (25-300) mm² 8.7/15 kV

Cu / XLPE / CTS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 35 sqmm supplied in wooden drum @ 1000 m
50 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 47.0 2,592
35 49.5 3,048
50 52.0 3,546
70 56.5 4,463
95 60.0 5,452
120 63.5 6,364
150 67.0 7,401
185 71.5 8,778
240 77.0 10,820
300 82.0 12,912

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.395 154 145 3.58 1.03
35 0.524 0.668 0.374 186 173 5.01 1.03
50 0.387 0.494 0.359 221 204 7.15 1.03
70 0.268 0.342 0.338 275 249 10.01 1.03
95 0.193 0.247 0.324 332 297 13.59 1.03
120 0.153 0.196 0.312 381 337 17.16 1.03
150 0.124 0.159 0.302 432 378 21.45 1.37
185 0.0991 0.128 0.294 491 425 26.46 1.37
240 0.0754 0.098 0.283 576 491 34.32 1.37
300 0.0601 0.080 0.275 654 551 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information