N2XSEY 3 x (25-300) mm² 6/10 kV

Cu / XLPE / CTS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, PVC Sheathed)
Standard Specification : SNI IEC 60502-2 : 2009

Application

Indoors, cable trunking, outdoors and in ground;
For power stations, industry and switchgear.

Special Features on Request :
• Oil Resistance
• Fire Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 41.0 2,153
35 44.0 2,618
50 46.5 3,101
70 50.5 3,927
95 55.0 4,957
120 58.5 5,841
150 62.0 6,858
185 66.0 8,132
240 71.5 10,156
300 76.5 12,205

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.368 152 145 3.58 1.03
35 0.524 0.668 0.349 183 173 5.01 1.03
50 0.387 0.494 0.335 218 204 7.15 1.03
70 0.268 0.342 0.316 272 249 10.01 1.03
95 0.193 0.247 0.303 328 297 13.59 1.03
120 0.153 0.196 0.293 377 337 17.16 1.03
150 0.124 0.160 0.284 428 378 21.45 1.03
185 0.0991 0.128 0.277 488 426 26.46 1.37
240 0.0754 0.099 0.267 572 491 34.32 1.37
300 0.0601 0.080 0.261 651 551 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information