N2XSEKBY 3 x (25-300) mm² 3.6/6 kV

Cu / XLPE / CTS / PVC / LS / PVC / DSTA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Double Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and low mechanical damage may
occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 44.0 4,623
35 47.0 5,392
50 50.0 6,265
70 54.5 7,617
95 58.5 9,069
120 63.0 10,531
150 67.0 12,092
185 71.0 14,008
240 77.5 16,909
300 86.0 21,161

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.342 153 145 3.58 1.03
35 0.524 0.668 0.325 185 173 5.01 1.03
50 0.387 0.494 0.313 220 203 7.15 1.03
70 0.268 0.342 0.296 273 248 10.01 1.03
95 0.193 0.247 0.285 329 295 13.59 1.03
120 0.153 0.196 0.276 377 334 17.16 1.03
150 0.124 0.160 0.268 427 373 21.45 1.03
185 0.0991 0.128 0.262 484 419 26.46 1.03
240 0.0754 0.099 0.255 563 479 34.32 1.37
300 0.0601 0.080 0.252 633 529 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information