N2XSEKFGbY 3 x (25-300) mm² 3.6/6 kV

Cu / XLPE / CTS / PVC / LS / PVC / SFWA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol.
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 44.5 4,873
35 47.5 5,663
50 50.5 6,555
70 55.0 7,912
95 59.0 9,372
120 63.0 10,887
150 67.0 12,484
185 71.5 14,406
240 78.0 17,343
300 85.0 20,836

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.342 153 145 3.58 1.03
35 0.524 0.668 0.325 185 173 5.01 1.03
50 0.387 0.494 0.313 220 203 7.15 1.03
70 0.268 0.342 0.296 273 248 10.01 1.03
95 0.193 0.247 0.285 329 295 13.59 1.03
120 0.153 0.196 0.276 377 334 17.16 1.03
150 0.124 0.160 0.268 426 373 21.45 1.03
185 0.0991 0.128 0.262 483 418 26.46 1.03
240 0.0754 0.099 0.255 562 478 34.32 1.37
300 0.0601 0.080 0.252 632 530 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information