N2XSEKY 3 x (25-300) mm² 3.6/6 kV

Cu / XLPE / CTS / PVC / LS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 sqmm supplied in wooden drum @ 1000 m
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 40.0 3,806
35 43.0 4,495
50 46.0 5,306
70 50.5 6,520
95 54.5 7,887
120 58.5 9,259
150 62.0 10,708
185 66.0 12,470
240 72.5 15,194
300 79.5 18,433

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.342 152 146 3.58 1.03
35 0.524 0.668 0.325 185 175 5.01 1.03
50 0.387 0.494 0.313 220 205 7.15 1.03
70 0.268 0.342 0.296 274 251 10.01 1.03
95 0.193 0.247 0.285 332 299 13.59 1.03
120 0.153 0.196 0.276 381 339 17.16 1.03
150 0.124 0.160 0.268 433 380 21.45 1.03
185 0.0991 0.128 0.262 494 428 26.46 1.03
240 0.0754 0.099 0.255 579 493 34.32 1.37
300 0.0601 0.080 0.252 656 551 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information