N2XSEBY 3 x (25-300) mm² 6/10 kV

Cu / XLPE / CTS / PVC / STA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation indoor, in ground direct burried,
for power station and switchgear, if there is a
risk that low mechanical damage may occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 43.0 2,767
35 46.0 3,279
50 48.5 3,799
70 52.5 4,687
95 56.5 5,753
120 60.0 6,690
150 63.5 7,761
185 67.5 9,091
240 73.0 11,235
300 78.0 13,326

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.368 154 146 3.58 1.03
35 0.524 0.668 0.349 186 175 5.01 1.03
50 0.387 0.494 0.335 222 205 7.15 1.03
70 0.268 0.342 0.316 276 251 10.01 1.03
95 0.193 0.247 0.303 333 299 13.59 1.03
120 0.153 0.196 0.293 382 339 17.16 1.03
150 0.124 0.160 0.284 433 380 21.45 1.03
185 0.0991 0.128 0.277 493 427 26.46 1.37
240 0.0754 0.099 0.267 576 491 34.32 1.37
300 0.0601 0.080 0.261 654 550 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information