N2XSEBY 3 x (25-300) mm2 8.7/15 kV

Cu / XLPE / CTS / PVC / STA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation indoor, in ground direct burried,
for power station and switchgear, if there is a
risk that low mechanical damage may occur.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 sqmm supplied in wooden drum @ 1000 m
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 48.5 3,293
35 51.0 3,790
50 53.5 4,324
70 58.0 5,310
95 61.5 6,354
120 65.0 7,321
150 69.0 8,412
185 73.0 9,854
240 78.5 11,980
300 85.0 14,914

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.395 156 146 3.58 1.03
35 0.524 0.668 0.374 189 174 5.01 1.03
50 0.387 0.494 0.359 224 205 7.15 1.03
70 0.268 0.342 0.338 278 250 10.01 1.03
95 0.193 0.247 0.324 336 298 13.59 1.03
120 0.153 0.196 0.312 385 339 17.16 1.03
150 0.124 0.159 0.302 436 379 21.45 1.37
185 0.0991 0.128 0.294 495 426 26.46 1.37
240 0.0754 0.098 0.283 578 490 34.32 1.37
300 0.0601 0.080 0.275 654 546 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information