N2XSEBY 3 x (50-300) mm² 18/30 kV

Cu / XLPE / CTS / PVC / STA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation indoor, in ground direct burried,
for power station and switchgear, if there is a
risk that low mechanical damage may occur.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
50 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
50 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
50 71.0 6,335
70 75.0 7,435
95 79.0 8,574
120 83.5 10,439
150 87.0 11,661
185 91.0 13,200
240 96.5 15,483
300 102.0 17,950

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
50 0.387 0.494 0.421 229 204 7.15 1.37
70 0.268 0.342 0.396 282 249 10.01 1.37
95 0.193 0.247 0.378 340 297 13.59 1.37
120 0.153 0.196 0.364 390 336 17.16 1.37
150 0.124 0.159 0.351 441 376 21.45 1.37
185 0.0991 0.128 0.340 500 423 26.46 1.37
240 0.0754 0.098 0.326 582 486 34.32 1.37
300 0.0601 0.079 0.315 656 543 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information