N2XSEFGbY 3 x (25-300) mm² 8,7/15 kV

Cu / XLPE / CTS / PVC / SFWA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 sqmm supplied in wooden drum @ 1000 m
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 49.0 3,552
35 51.5 4,072
50 54.0 4,606
70 58.5 5,619
95 62.0 6,697
120 65.5 7,705
150 69.0 8,810
185 73.0 10,284
240 79.0 12,429
300 83.5 14,586

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.395 156 146 3.58 1.03
35 0.524 0.668 0.374 189 174 5.01 1.03
50 0.387 0.494 0.359 225 205 7.15 1.03
70 0.268 0.342 0.338 278 250 10.01 1.03
95 0.193 0.247 0.324 336 298 13.59 1.03
120 0.153 0.196 0.312 385 338 17.16 1.03
150 0.124 0.159 0.302 435 378 21.45 1.37
185 0.0991 0.128 0.294 494 424 26.46 1.37
240 0.0754 0.098 0.283 577 488 34.32 1.37
300 0.0601 0.080 0.275 654 547 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information