N2XSERY 3 x (25-300) mm² 6/10 kV

Cu / XLPE / CTS / PVC / SWA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.

Special Features on Request :
• Oil Resistance
• Fire Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 sqmm supplied in wooden drum @ 1000 m
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 46.5 3,907
35 50.0 4,496
50 52.5 5,103
70 56.5 6,093
95 60.5 7,262
120 64.0 8,309
150 67.5 9,448
185 71.0 10,884
240 78.5 14,033
300 83.5 16,345

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.368 158 148 3.58 1.03
35 0.524 0.668 0.349 191 176 5.01 1.03
50 0.387 0.494 0.335 227 207 7.15 1.03
70 0.268 0.342 0.316 281 253 10.01 1.03
95 0.193 0.247 0.303 339 301 13.59 1.03
120 0.153 0.196 0.293 389 341 17.16 1.03
150 0.124 0.160 0.284 440 382 21.45 1.03
185 0.0991 0.128 0.277 501 430 26.46 1.37
240 0.0754 0.099 0.267 585 493 34.32 1.37
300 0.0601 0.080 0.261 663 551 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information