N2XSERY 3 x (25-300) mm² 8.7/15 kV

Cu / XLPE / CTS / PVC / SWA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Galvanized Steel Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 52.5 4,594
35 55.0 5,174
50 57.5 5,755
70 62.0 6,876
95 65.5 7,989
120 69.0 9,065
150 73.0 10,266
185 78.5 12,655
240 84.0 14,959
300 89.0 17,314

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.395 159 147 3.58 1.03
35 0.524 0.668 0.374 192 176 5.01 1.03
50 0.387 0.494 0.359 229 207 7.15 1.03
70 0.268 0.342 0.338 283 252 10.01 1.03
95 0.193 0.247 0.324 341 300 13.59 1.03
120 0.153 0.196 0.312 391 341 17.16 1.03
150 0.124 0.159 0.302 442 381 21.45 1.37
185 0.0991 0.128 0.294 503 428 26.46 1.37
240 0.0754 0.098 0.283 587 492 34.32 1.37
300 0.0601 0.080 0.275 664 550 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information