N2XSR(AL)Y 1 x (25-630) mm² 6/10 kV

Cu / XLPE/ CTS / PVC / AWA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Aluminium Wire Armor,PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For installation in the ground, indoors, cable
trunking and outdoors if increased mechanical
protection is required or where high-pulling
stresses may occur during installation or
operation.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Note :
Conductor Shape
25 - 630 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 240 sqmm supplied in wooden drum @ 1000 m
300 - 630 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 25.0 917
35 26.0 1,051
50 27.0 1,196
70 29.0 1,468
95 30.5 1,768
120 32.0 2,007
150 34.5 2,412
185 36.5 2,842
240 39.0 3,465
300 41.5 4,049
400 45.0 4,939
500 50.0 6,258
630 53.5 7,723

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
Trefoil formation
Flat formation
in air in ground in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) (mH/km) Max. (A) Max. (A) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.467 0.513 169 154 172 157 3.58 1.14
35 0.524 0.668 0.443 0.489 204 184 209 187 5.01 1.14
50 0.387 0.494 0.425 0.471 243 216 248 220 7.15 1.14
70 0.268 0.342 0.401 0.447 302 263 308 268 10.01 1.14
95 0.193 0.247 0.383 0.430 365 313 372 318 13.59 1.14
120 0.153 0.196 0.369 0.415 419 353 426 358 17.16 1.14
150 0.124 0.159 0.362 0.409 475 392 481 396 21.45 1.14
185 0.0991 0.128 0.353 0.399 538 438 543 440 26.46 1.14
240 0.0754 0.098 0.340 0.386 627 500 629 498 34.32 1.14
300 0.0601 0.079 0.329 0.375 706 554 705 549 42.90 1.14
400 0.0470 0.063 0.316 0.363 805 616 798 606 57.20 1.14
500 0.0366 0.050 0.313 0.360 895 664 878 646 71.50 1.14
630 0.0283 0.041 0.304 0.350 995 721 969 695 90.09 1.14

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information