N2XSEKFGbY 3 x (25-300) mm² 6/10 kV

Cu / XLPE / CTS / PVC / LS / PVC / SFWA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol.
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen

Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 49.0 5,817
35 52.0 6,558
50 55.0 7,451
70 59.5 8,869
95 64.0 10,490
120 68.0 11,990
150 72.0 13,644
185 76.0 15,560
240 82.5 18,581
300 88.0 21,818

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.368 155 145 3.58 1.03
35 0.524 0.668 0.349 187 173 5.01 1.03
50 0.387 0.494 0.335 222 203 7.15 1.03
70 0.268 0.342 0.316 275 248 10.01 1.03
95 0.193 0.247 0.303 331 294 13.59 1.03
120 0.153 0.196 0.293 379 333 17.16 1.03
150 0.124 0.160 0.284 428 372 21.45 1.03
185 0.0991 0.128 0.277 486 417 26.46 1.37
240 0.0754 0.099 0.267 562 476 34.32 1.37
300 0.0601 0.080 0.261 633 529 42.90 1.37