N2XSEKFGbY 3 x (25-300) mm² 8.7/15 kV

Cu / XLPE / CTS / PVC / LS / PVC / SFWA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol.
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 55.5 6,963
35 58.5 7,866
50 61.0 8,815
70 66.0 10,407
95 69.5 11,975
120 73.5 13,335
150 77.5 15,062
185 82.0 17,175
240 88.5 20,453
300 93.5 23,487

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.395 157 144 3.58 1.03
35 0.524 0.668 0.374 189 172 5.01 1.03
50 0.387 0.494 0.359 224 203 7.15 1.03
70 0.268 0.342 0.338 277 247 10.01 1.03
95 0.193 0.247 0.324 334 294 13.59 1.03
120 0.153 0.196 0.312 381 333 17.16 1.03
150 0.124 0.159 0.302 429 371 21.45 1.37
185 0.0991 0.128 0.294 486 415 26.46 1.37
240 0.0754 0.098 0.283 564 475 34.32 1.37
300 0.0601 0.080 0.275 634 528 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information