N2XSEKFGbY 3 x (35-300) mm² 12/20 kV

Cu / XLPE / CTS / PVC / LS / PVC / SFWA / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol.
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and high pulling stresses may occur
during installation.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
35 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
35 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
35 63.5 9,030
50 67.0 10,066
70 71.0 11,643
95 75.0 13,297
120 79.0 14,910
150 83.5 16,810
185 87.5 18,935
240 93.5 21,986
300 99.0 25,141

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
35 0.524 0.668 0.395 190 172 5.01 1.03
50 0.387 0.494 0.379 225 202 7.15 1.03
70 0.268 0.342 0.357 278 247 10.01 1.03
95 0.193 0.247 0.341 335 293 13.59 1.37
120 0.153 0.196 0.328 383 332 17.16 1.37
150 0.124 0.159 0.318 430 370 21.45 1.37
185 0.0991 0.128 0.308 487 414 26.46 1.37
240 0.0754 0.098 0.296 565 474 34.32 1.37
300 0.0601 0.079 0.287 634 526 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information