N2XSEKY 3 x (25-300) mm2 6/10 kV


Cu / XLPE / CTS / PVC / LS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.

Special Features on Request :
• Fire Resistance
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 45.0 4,627
35 48.0 5,265
50 50.5 6,056
70 55.0 7,351
95 59.0 8,826
120 63.0 10,177
150 66.5 11,677
185 70.5 13,493
240 77.0 16,300
300 82.5 19,324

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.368 155 146 3.58 1.03
35 0.524 0.668 0.349 187 174 5.01 1.03
50 0.387 0.494 0.335 223 205 7.15 1.03
70 0.268 0.342 0.316 277 251 10.01 1.03
95 0.193 0.247 0.303 334 299 13.59 1.03
120 0.153 0.196 0.293 385 339 17.16 1.03
150 0.124 0.160 0.284 436 380 21.45 1.03
185 0.0991 0.128 0.277 497 428 26.46 1.37
240 0.0754 0.099 0.267 580 492 34.32 1.37
300 0.0601 0.080 0.261 658 551 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information