N2XSEKY 3 x (25-300) mm² 8.7/15 kV

Cu / XLPE / CTS / PVC / LS / PVC
(Copper Conductor, XLPE Insulated, Copper Tape Screen, Lead Sheathed, PVC Sheathed)
Standard Specification : IEC 60502-2

Application

For indoor, outdoor, in ground and in duct.
Mainly on chemical industries, refineries, petrol
stations and any other locations where there is
a risk that solvent, fuel and other chemicals may
penetrate and mechanical damage is not likely
to occur.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape

Standard Packing
25 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
25 50.5 5,566
35 53.5 6,361
50 56.5 7,209
70 61.0 8,669
95 65.0 10,144
120 68.5 11,353
150 72.0 12,915
185 76.5 14,896
240 82.5 17,956
300 88.0 20,818

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
in air in ground Conductor Screen
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) Max. (A) Max. (A) Max. (kA) Max. (kA)
25 0.727 0.927 0.395 157 146 3.58 1.03
35 0.524 0.668 0.374 190 174 5.01 1.03
50 0.387 0.494 0.359 226 205 7.15 1.03
70 0.268 0.342 0.338 279 250 10.01 1.03
95 0.193 0.247 0.324 338 299 13.59 1.03
120 0.153 0.196 0.312 387 339 17.16 1.03
150 0.124 0.159 0.302 439 380 21.45 1.37
185 0.0991 0.128 0.294 498 427 26.46 1.37
240 0.0754 0.098 0.283 582 491 34.32 1.37
300 0.0601 0.080 0.275 660 550 42.90 1.37

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information