aluminium Conductors

AAC EC 1350
All Aluminium Conductor EC 1350

Standard Specification : DIN EN 50182 : 2001

Technical Properties

Size Number / Dia.
of Wire
Calculated
Cross Sect.
Area
Approx.
Overall
Diameter
Approx.
Weight
Calculated
Breaking Load
DC Resistance
at 20° C
Max.
Current
Carrying
Capacity *
Standard
Length
per Reel
mm²
No. / mm
mm²
mm
kg/km
kN Ohm/km A m
25 7 / 2.10 24.2 6.30 66 4.36 1.1787 144 2,000
35 7 / 2.50 34.4 7.50 94 6.01 0.8317 180 2,000
50 7 / 3.00 49.5 9.00 135 8.41 0.5776 225 2,000
70 19 / 2.10 65.8 10.50 181 11.85 0.4367 270 2,000
95 19 / 2.50 93.3 12.50 256 16.32 0.3081 340 2,000
120 19 / 2.80 117.0 14.00 322 19.89 0.2456 390 2,000
150 37 / 2.25 147.1 15.75 405 26.48 0.1960 455 2,000
185 37 / 2.50 181.6 17.50 500 31.78 0.1588 520 2,000
240 61 / 2.25 242.5 20.25 669 43.66 0.1193 625 2,000
300 61 / 2.50 299.4 22.50 826 52.40 0.0966 710 2,000
400 61 / 2.89 400.1 26.01 1,104 68.02 0.0723 855 2,000
450 61 / 3.07 451.5 27.63 1,246 74.50 0.0641 925 2,000
500 61 / 3.23 499.8 29.07 1,379 82.47 0.0579 990 2,000
625 91 / 2.96 626.2 32.56 1,733 106.45 0.0464 1,140 2,000
800 91 / 3.35 802.1 36.85 2,219 132.34 0.0362 1,340 2,000
1000 91 / 3.74 999.7 41.14 2,766 159.95 0.0291 1,540 1,000
*Note :
Ambient temperature
: 35°C Continuous operating temperature of conductor : 80°C
wind velocity : 0.6 m/sec Conductivity of Al : 61 % IACS