N2XB(AL)Y 1 x (16-800) mm² 0.6/1 kV

Cu / Mica / XLPE / DATA / PVC
(Copper Conductor, Mica Tape, XLPE Insulated, Double Aluminium Tape Armor, PVC Sheathed)
Standard Specification : IEC 60502-1 and IEC 60331

Application

For wiring of fire resistant safety circuits, such
as fire alarm system, emergency lighting and
power, public address and emergency voice
communication systems in highrise building,
control and instrumentation services in industrial,
commercial and residential complexes.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen


Note :
Conductor Shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 800 sqmm supplied in non compacted circular stranded (rm) or compacted circular stranded (cm) conductor shape

Standard Packing
16 - 300 sqmm supplied in wooden drum @ 1000 m
400 - 800 sqmm supplied wooden drum on available length
Length Tolerance per drum ± 2%

Construction Data

Nom. Cross Section Area Overall Diameter Cable Weight
approx.
approx.
mm²
mm
kg/km
16
15.5 386
25
16.9 494
35
18.0 602
50
19.4 749
70
21.5 988
95
23.5 1,254
120
25.5 1,535
150
27.5 1,823
185
30.0 2,209
240
33.0 2,864
300
36.0 3,445
400
39.5 4,358
500 44.0 5,465
630 48.5 6,968
800 54.0 8,765

Electrical Data

Conductor Inductance Current - Carrying Capacity at 30° C * Short circuit current at 1 sec
Nom. Cross Section Area
DC Resistance at 20°C
AC Resistance at 90°C
Trefoil formation
Flat formation
in air in ground in air in ground
(mm²)
Max. (Ω/km)
Max. (Ω/km)
(mH/km) (mH/km) Max. (A) Max. (A) Max. (A) Max. (A) Max. (kA)
16
1.15 1.466 0.414 0.460 118 118 121 121 2.29
25
0.727 0.927 0.385 0.431 154 153 158 157 3.58
35
0.524 0.668 0.366 0.412 188 183 193 188 5.01
50
0.387 0.494 0.348 0.394 229 217 235 223 7.15
70
0.268 0.342 0.331 0.377 287 265 295 272 10.01
95
0.193 0.247 0.316 0.362 352 317 361 324 13.59
120
0.153 0.196 0.307 0.353 407 359 418 367 17.16
150
0.124 0.159 0.302 0.348 465 402 476 410 21.45
185
0.0991 0.128 0.296 0.342 537 453 549 461 26.46
240
0.0754 0.098 0.287 0.333 636 523 648 529 34.32
300
0.0601 0.079 0.281 0.327 728 585 739 590 42.90
400
0.0470 0.064 0.278 0.325 838 655 846 657 57.20
500 0.0366 0.051 0.273 0.319 960 731 964 728 71.50
630 0.0283 0.042 0.267 0.313 1092 807 1087 797 90.09
800 0.0221 0.035 0.264 0.310 1216 877 1202 858 114.40

*Further information about rating factor for certain cable arrangement can be found on supplementary technical information