J Type Thermocouple Extension Cable
JXYY (1-50) Pairs x 1.5 mm² 300 V

(Iron-Constantan Conductor, PVC Insulated, Individual or Collective Screen, PVC Sheathed)
Standard Specification : IEC 60584, ANSI MC 96.1

Application

For transmission of thermoelectric voltage from measuring junction to reference junction.

Special Features on Request :
• Oil Resistance
• UV Resistance
• Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
• Heat Resistance
• Anti Termite
• Anti Rodent
• Low Smoke Zero Halogen
• Nylon Coated


Fig. 01 : Collective Screen

Fig. 02 : Individual Screen

Note :
Conductor Shape
All construction supplied in solid (re) or circular stranded (rm)

Standard Packing
All conductor supplied in wooden drum @ 1000 m
Length tolerance per drum ± 2%
Size of drain wire : 0.5 mm²

Construction Data

No.
of
pairs
Size
1.5 mm2
Collective Screen Individual Screen
Overall
Diameter

Cable
Weight
Overall
Diameter
Cable
Weight
approx.
approx. approx. approx.
mm
kg/km
mm
kg/km
1 9.9 136 - -
2 12.8 197 14.6 311
3 14.9 240 15.5 357
4 16.7 299 16.9 419
5 18.3 382 18.5 423
6 19.7 425 21.5 522
7 21.0 468 21.5 536
9 23.5 576 25.5 676
10 25.0 641 27.5 757
12 27.0 748 30.0 888
14 29.0 866 31.5 1,022
15 30.0 946 33.5 1,114
16 30.5 999 35.0 1,188
18 32.5 1,091 37.5 1,305
19 33.0 1,143 37.5 1,360
20 34.0 1,238 39.5 1,537
24 37.0 1,437 46.5 1,755
30 41.0 1,766 49.5 2,134
36 45.0 2,115 54.0 2,556
40 47.5 2,325 56.0 2,803
48 51.5 2,781 63.0 3,370
50 52.5 2,884 64.5 3,498

Material & Color Code

Type JX
Material ( + )
Iron
( - ) Constantan
Limit of Error -
(Temp. Range)
IEC 60584 Class 1
µ 1.5 °C / µ 85 ØV ( -25 ~ 200 °C)
Class 2 µ 2.5 °C / µ 140 ØV ( -25 ~ 200 °C)
ANSI MC - 96.1 Standard
µ 2.2 °C ( 0 ~ 200 °C )
Special µ 1.1 °C ( 0 ~ 200 °C )
Color Code Insulation ( + )
White
( - ) Red
Jacket Black

Electrical Data

Conductor AC
Normal
Cross
Section
Nominal Value
Loop Resistance
at 20 °C
Voltage
Test
mm2
/km volt/1 min.
1.5 418 1000